← All Products Extra Low Temp Series

ELT Series

Air-cooled extra low temperature chillers for sub-zero process cooling. Copeland Scroll compressor, R448a refrigerant, ETL listed and ISO 9001:2015 certified. Made in the USA.

-22°F Min Temp  /  -30°C
ETL Listed ISO 9001:2015 Made in USA UL/CSA Certified
AG Chill ELT Series Extra Low Temp Chiller
Verified Performance Data

Cooling Capacity at 70°F Ambient

AG2000-ELT (2 Ton reference model). Performance scales proportionally across the series.

At -22°F / -30°C

9,764 BTU/hr

2,860 Watts

At -4°F / -20°C

13,126 BTU/hr

3,850 Watts

At 14°F / -10°C

16,749 BTU/hr

4,910 Watts

Pump Performance

0 GPM

@ 32 PSI (max head)

22.5 GPM

@ 24 PSI

45 GPM

@ 7 PSI (max flow)

AG2000-ELT

Standard Features & Specifications

All information for reference only. Specifications subject to change without notice.

Dimensions — AG2000-ELT

DepthWidthHeightWeightTank CapacityFluid Connections
30.94"43.63"40.32"650 lbs15 Gal Stainless Steel3/4" NPT
SpecificationValue
Performance
Working Temperature Range-22°F (-30°C) to 14°F (-10°C)
Temperature Stability±2°F
Ambient Temperature Range40°F – 100°F
Refrigeration Circuit
CompressorCopeland Scroll
RefrigerantR448a
Heat ExchangerBrazed Plate Heat Exchanger
Additional FeaturesAccess Ports, Service Valves, Filter Drier, Sight Glass, Liquid Receiver, High/Low Pressure Controls, TXV
Process Fluid Circuit
PumpContinuous Duty, 3/4 HP Centrifugal Pump
Inlet / Outlet3/4" NPT
Reservoir15 Gallon Stainless Steel
Additional FeaturesInline Strainer, Process Fluid Temperature Sensor, Pump Discharge Pressure Gauge, Internal Fluid Bypass Valve
User Interface
ControlsElectronic Programmed Temperature Controller with Constant Setpoint & Process Temperature Readout
Additional FeaturesFluid Level Indicator, Pump Pressure Gauge
Construction
FrameGalvanized Steel
EnclosurePowder Coated Steel with Easy Access Panels
Quality & Certifications
UL/CSA CertificationETL 3170655, UL STD 1994, CAN/CSA STD C22.2 No. 236
ManufacturingManufactured in the U.S.A.  ·  ISO 9001:2015 Certified
Warranty1 Year Standard Warranty
Power
208-240VAC / 3P / 60HzFLA23.8 Amps  ·  MCA: 33 Amps
480VAC / 3P / 60HzFLA11.9 Amps  ·  MCA: 16 Amps

Optional Upgrades

Anti-Backflow Process Heating Pass-through External Temperature Monitoring Alternate Pumps Controllers

More options and customization available. Contact factory for more information.

Series Range

Available ELT Models

The AG2000-ELT is the standard 2-ton extra-low-temp model. Larger UL/CSA-certified and custom configurations are available up to 30 tons — contact AG Chill.

ModelDescriptionWorking Temp RangeSpec Sheet
AG0500-ELT0.5 Ton Air Cooled Extra Low Temp-22°F to 14°FContact factory
AG1000-ELT1 Ton Air Cooled Extra Low Temp-22°F to 14°FContact factory
AG2000-ELT2 Ton Air Cooled Extra Low Temp-22°F to 14°FSpec Above
AG5000-ELT5 Ton Air Cooled Extra Low Temp-22°F to 14°FContact factory
AG10000-ELT10 Ton Air Cooled Extra Low Temp-22°F to 14°FContact factory
AG20000-ELT20 Ton Air Cooled Extra Low Temp-22°F to 14°FContact factory
Get Started

Request a Full Spec Sheet or Custom Quote

Full spec sheets available for all ELT models. Custom configurations available — contact the factory for more information.

Request Spec Sheets Custom Build Request
Resources

Related Guides

Guide
Chiller Requirements for Ethanol Extraction
How to size and select a chiller for ethanol extraction — target temperatures, why deeper is cleaner, and matching…
Guide
How to Size an Industrial Chiller
How to size an industrial chiller: heat load, flow rate, temperature differential, and ambient conditions — and how…
FAQ

Common Questions

What is the ELT (Extra Low Temp) series for?

ELT reaches about −22°F (−30°C) — mid-range ethanol extraction and sub-zero process cooling.

What refrigerant does the ELT series use?

ELT uses R-448A; confirm the exact configuration with an engineer for your temperature and load.